InstallatIon
These valves should not be installed in systems that
exceed the ANSI specified temperature and pressure
ratings. Inspect the valves for shipping, damage and
foreign debris when uncrating.
Be sure to use proper hoists with chains or slings
when uncrating and handling these valves. Refer to
Table 1 in the data sheet for valve body weights.
1. Ensure the pipe is free from welding slag,
chips and other debris by blowing out the line
prior to installation.
2. Install approved gaskets between the valve
body and the pipeline flanges. For butt weld
ends on the Mark ET Series trim configuration,
remove gaskets and seal rings prior to welding
the body into the pipeline.
3. For continuous service applications, Jordan
Valve recommends a standard three-valve
maintenance bypass be installed. This
allows isolation of the valve body without
shutting down the pipeline system.
4. The valve should be positioned on the
line so the flow direction indicator
corresponds to the direction of flow in the
pipeline.
Note: The effectiveness of the pressure-energized
seal will be compromised if return ow exists
where the downstream pressure exceeds up-
stream pressure. The result could be leakage or
damage to the seal.
5. The valve body should be positioned with
the actuator vertically above it. It
is possible to position the valve with an
orientation below vertical with support
supplied for the actuator. Support for the
actuator is required if there is excessive
vibration in the line, or if the valve body is
positioned more than 45 degrees off
vertical.
IntroductIon
Contained in this manual are installation instructions,
maintenance and parts information for the Mark H-900,
H-1500 and H-2500 Series Valve Bodies. Refer to the
appropriate manuals for instructions for the accompa-
nying actuator, positioner and additional accessories.
Only trained or experienced personnel should carry
out the operation and installation of all pressure equip-
ment. If you have any questions regarding the equip-
ment, contact your Jordan Valve representative. A
serial number identifies each Mark H Series valve and
is stamped on the valve body. Please reference this
number when communicating with your Jordan Valve
representative.
I & M Mark H-900, H-1500 and
H-2500 Series
3170 Wasson Road • Cincinnati, OH 45209
Phone 513.533.5600 • Fax 513.871.0105 (f)
[email protected] • www.jordanvalve.com
Installation & Maintenance Instructions for the
Mark H-900, H-1500 and H-2500 Series Globe
Style Control Valves
Warning: Jordan Valve Control Valves must only be used, installed and repaired in accordance with these Installa-
tion & Maintenance Instructions. Observe all applicable public and company codes and regulations. In the event
of leakage or other malfunction, call a qualified service person; continued operation may cause system failure or
a general hazard. Before servicing any valve, disconnect, shut off, or bypass all pressurized fluid. Before disassem-
bling a valve, be sure to release all spring tension.
Vue de la page 0
1 2 3 4 5 6 ... 12 13

Résumé du contenu

Page 1 - IntroductIon

InstallatIonThese valves should not be installed in systems that exceed the ANSI specified temperature and pressure ratings. Inspect the valves for sh

Page 2 - Parts reference

-10-Key 7: Body Cont, CF8MANSI Body RatingEnd ConnectionsBody Size, InchesWithout Drain Plug Tapping3 4Class H-900 and Class H-1500900 lb RF 30A5287X0

Page 3 - MaIntenance

Key 10: Groove Pin, 316 SST*Port Size Valve Stem Connection ED, ETin mm in mm1-5/16 33.3 1/2 12.7 1V3226350721-7/8 47.6 1/2 12.7 1V3227350723/4 19.1 2

Page 4

-12-ANSI Body RatingBody Size (in)Upper Retainer316 SSLower Retainer316 SSSeal KitsViton* HSNClass H-900 and H-15003 13A0295X012 13A0297X012 3H1500-SK

Page 5 - Trim Maintenance

Key 21: Packing Set*Boss Size Stem Size Spring-LoadedTFE V-RingDoubleTFE V-Ring(2 req’d)in mm in mm2-13/16 71.4 1/2 12.7 1R290201012 1R2902010123-9/16

Page 6 - Parts orderIng

Mark H-900, H-1500 and H-2500 Control ValVes-2-Key Description1 Drive Screws2 Flow Arrow3 Valve Stem4 Bonnet Gasket5 Cage Gasket6 Inner Piston Ring6a

Page 7

-3-MaIntenanceInternal valve components are subject to normal deterio-ration and must be inspected and replaced as required. The necessity of inspecti

Page 8

-4-Packing Replacement cont'd9. Use a packing hook to remove the packing parts, or push them toward the top of the bon- net using a small r

Page 9

-5-Trim MaintenanceRefer to this section for instructions regarding disas-sembly, replacement of valve plug parts, grinding metal seats and assembly o

Page 10

-6-Lapping Metal SeatsWhile some leakage is expected with any metal-to-metal seating in a valve body, excessive leakage can be improved by lapping or

Page 11

-7-Mark H-900, H-1500 and H-2500 serIes desIgn ValVe BodIesKey Description Part Number1 Drive Screws, SST (2 req’d) 1A3682289822 Flow Arrow, SST 1V106

Page 12 - * Recommended Spare Part

-8-Key Description Part Number21 Packing Set See Following Tables22 Lantern Ring or Spring See Following Tables23 Special Washer See Following Tables2

Page 13 - MKH-900,1500,2500/0214/2K

-9-ANSI Body RatingBody Size (In)Port Size Mark ED Piston Ring Mark ET Seal Ringin mmAlloy #25 and17-4 PH SST450oF to 800oF(232oC to 427oC)Spring-Load